The tab allows you to define push targets for heartbeat signals. You must create a binary or analog point in the MSEA system to receive heartbeat commands from E2H.
You can only define targets for BV, BO, AV, and AO point types.
Click the “Add” button to create a target:
Item Reference
Enter the fully qualified item reference for the target point in MSEA.
Point Type
Enter the point type for the target. Only BV, BO, AV, AO types are allowed.
Priority
Enter the priority of the command (16 default)
Heartbeat Type
There are two types of output for the heartbeat:
Ping: Sends a single command every 5 minutes. (Binary 1, Analog 100)
Toggle Value: Sends alternating commands every 5 minutes. (Binary 0/1, Analog 0/100)
Test Button
After you have defined the point parameters and the point exists in the MSEA system, click the test button to send a command to the point.
You can define multiple targets so that you can send commands to building controllers to improve reliability in the case if one controller becomes offline.