StartStop Action

The StartStop action sends a WriteProperty web service command to a single MSEA object for each side (start and stop) of an event.  The Start value is sent to the object when an Event Start or Event Setup Start has been triggered.  The Stop value is sent to the object when an Event Stop or Event Teardown Stop has occurred.

If the Release checkbox is selected, the priority command issued for the event start will be cleared and released at the end of the event.  This allows lower priority commands (like a default base schedule) to take over.

 

This action only applies to the following event triggers

      EventStartStop

      EventSetupTeardown

      ZoneFirstLastEventStartStop

      ZoneFirstLastSetupTeardown

 

  Field Name

  Description

  Range

Item Reference

The fully qualified item reference of the device that holds the point object that you want to command.

Example:

JCI-ADS1:NAE1/FC-1.AHU-1.OCC-CMD

Property

The MSEA property of the object to write to.

Example: Present Value

Priority

Priority value for commanding a commandable object and property.

1-16 (1=highest)

16 = Recommended default

Only applies to Present_Value property on commandable objects (ie. AO, AV, BO, BV, MSO, MSV)

Event Start

Value to write to the selected property when the START of the event is triggered.

Depends on object type.

Event Stop

Value to write to the selected property when the END of the event is triggered.

Depends on object type.

Release

To release the priority from the start command, check this box.  A NULL value will be displayed in the value for Event Stop.

Only applies to Present_Value property on commandable objects (ie. AO, AV, BO, BV, MSO, MSV)

 

Browse Link

Click on the Browse link to open the MSEA network browser.

Verify Link

Click on the Verify link to verify that the selected object and property can be read directly from the MSEA network without errors. The results of the verification will be shown in the Results window.

Test Link

Click on the Test link to attempt to write the define value to the object.  Select either “Test Event Start” or “Test Event Stop” to send the test command.  The results of the test will be shown in the Results window.