StartStop Action - CSV Column Headers Required

  Field Name

  Description

  Notes

action:equipmentname

Name of the equipment item as seen in the equipment manager.

Unique

action:devicename

Name of the device interface

BACnet Interface v2

action:name

Name of the particular action

StartStop

action:order

If multiple actions are present in the equipment item, this defines the order.

0

action:functionid

Custom event function that will activate this action.

This is normally blank.

action:triggername

Name of the trigger that executes the action

EventStartStop, EventSetupTeardown

action:objectname

Unique point object name

 

parm:deviceid

Bacnet device ID

integer

parm:objectid

BACnet object id

integer

parm:objectname

Object name of the bacnet object

This is populated when the “verify” button is used in the action form.

parm:objecttype

BACnet object type

Binary_Value, Binary_Output, Multistate_Value, Multistate_Output, Analog_Value, Analog_Output

parm:priority

Priority for sending command

1-16

parm:propertytype

Property to send write commands to

Present_Value

parm:arrayindex

Array index of enumerated values

Typically -1 unless the property type is a property array

parm:valuestart

Value to send on event start

Numeric value

parm:valuestop

Value to send on event stop

Numeric value, NULL (for release)

parm:actionstate

Not applicable

-1