Since there is no priority system in the Pelican Wireless thermostats, commands from E2H may be interrupted by schedules, events, or operator interaction. Here’s a matrix showing various modes and how commands from schedules, events, and E2H are handled.
|
Thermostat
|
E2H Occupied (Schedules=OFF) |
E2H Unoccupied Schedules=OFF |
E2H Unoccupied Schedules=ON |
E2H Unoccupied Schedules=Named |
User Commands |
|
“Occupied”
|
E2H or Event Schedule Cmds* |
E2H or Event Schedule Cmds* |
E2H cmd, then next Schedule. Events will override schedules |
E2H cmd, then next Named Schedule. Events will override schedules |
Immediate* |
|
“Vacant” with no vacation schedule |
E2H Cmd |
E2H Cmd |
E2H Cmd |
E2H Cmd |
Immediate* |
|
“Vacant” with a vacation schedule |
Active Vacation Cmds** |
Active Vacation Cmds** |
Active Vacation Cmds** |
Active Vacation Cmds** |
Immediate* |
*Last command wins
**Active vacation settings will be immediately applied