Default Metasys MSEA Priority Levels
Application |
Priority Level |
Manual Life Safety (BACnet standard) |
1 |
Auto Life Safety (BACnet standard) |
2 |
(Available) |
3 |
(Available) |
4 |
Critical Equipment (BACnet standard) |
5 |
Minimum On Off (BACnet standard) |
6 |
Heavy Equipment Delay |
7 |
Manual Operator Override (BACnet standard) |
8 |
(Available) |
9 |
(Available) |
10 |
Demand Limiting |
11 |
(Available) |
12 |
Load Rolling |
13 |
(Available) |
14 |
Scheduling |
15 |
Default (Adjust Command, State 1, etc.) |
16 |
When Events2HVAC sends a command to an object for an event, you want to set the appropriate priority for your particular system. If you want to override and scheduled commands for the events and let the schedule commands operated as a failsafe, then set your command priority to 14. If you want a schedule command to override anything the Events2HVAC commands, set your priority to 16.